TRIPLE E TRADING CO., LTD.
Fluke 1550C Insulation Resistance Tester
฿12330.00
Fluke 1550C Insulation Resistance Tester
เหลือ 99 ชิ้น
ซื้อเลย
หยิบลงตะกร้า
  • หมวดหมู่ : MegOhm Meters
  • รหัสสินค้า : 006684

รายละเอียดสินค้า Fluke 1550C Insulation Resistance Tester

 

Specifications
Insulation resistance measurement
Test voltage (dc) Range (dc) Accuracy (± reading)
250 V < 200 kΩ
200 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ
unspecified
5 %
20 %
unspecified
500 V <200 kΩ 
200 kΩ to 10 GΩ 
10 GΩ to 100 GΩ 
> 100 GΩ
unspecified
5 % 
20 % 
unspecified 
 
1000 V < 200 kΩ 
200 kΩ to 20 GΩ 
20 GΩ to 200 GΩ 
> 200 GΩ
unspecified
5 % 
20 % 
unspecified 
 
2500 V < 200 kΩ 
200 kΩ to 50 GΩ 
50 GΩ to 500 GΩ 
> 500 GΩ
unspecified
5 % 
20 % 
unspecified 
 
5000 V < 200 kΩ
200 kΩ to 100 GΩ 
100 GΩ to 1 TΩ
> 1 TΩ
 
unspecified
5 %
20 %
unspecified 
 
10000 V
(1555 only)
< 200 kΩ
200 kΩ to 200 GΩ 
10 GΩ to 2 TΩ 
> 2 TΩ
unspecified
5 %
20 %
unspecified 
 
Bar graph range 0 to 1 TΩ
Insulation test voltage accuracy -0 %, +10 % at 1 mA load current
Induced ac mains current rejection 2 mA maximum
Charging rate for capacitive load 5 seconds per μF
Discharge rate for capacitive load 1.5 s/μF
Leakage current measurement Range: 1 nA to 2 mA Accuracy: ± (5 % + 2 nA)
Capacitance measurement Range: 0.01 uF to 15.00 μF Accuracy: ± (15 % rdg + 0.03 μF)
Timer Range: 0 to 99 minutes Resolution Accuracy: 
Setting: 1 minute 
Indication: 1 second
Live circuit warning Warning Range: 
30 V to 660 V ac/dc, 
50/60 Hz
Voltage Accuracy: 
± (15 % + 2 V)
General specifications
Display 75 mm x 105 mm
Power 12 V lead-acid rechargeable battery, Yuasa NP2.8-12
Charger Input (AC) Charger Input (AC) 85 V to 250 V ac 50/60 HZ 20 VA

* This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord.
The protective earth terminal (ground pin) is not connected internally. The extra pin is for added 
plug retention only.

Dimensions 170 mm x 242 mm x 330 mm (6.7 in x 9.5 in x 13 in)
Weight 3.6 kg (7.94 lb)
Temperature (operating) -20 ºC to 50 ºC (-4 ºF to 122 ºF)
Temperature (storage) -20 ºC to 65 ºC (-4 ºF to 149 ºF)
Humidity 80 % to 31 ºC decreasing linearly to 50 % at 50 ºC
Altitude 2000 m
Enclosure sealing IP40
Input overload protection 1000 V ac
Input overload protection 1000 V ac
Electromagnetic compatibility EN 61326
Certifications   
Safety compliance CAT III 1000 V, CAT IV 600 V
Pollution degree 2