) 1. Be sure to remove the jumper across the inverter terminals P/+-P1. (A failure to do so will produce no power factor improving effect))
2. The wiring length between the reactor and inverter should be within 5m.
3. The size of the cables used should be equal to or larger than that of the power supply cables (R/L1, S/L2, T/L3).
4. Make selection according to the motor capacity.
(When the inverter capacity is larger than the motor capacity, make selection according to the motor capacity)
5. Power factor improving reactor (FR-BEL) can be used.
Power factor improving effect
FR-BEL approx.95%
FR-HEL approx.93%
6. Outline dimension drawing shown is a one of a typical model.
The shape differs according to each models.
7. Install the DC reactor (FR-HEL) on horizontal or vertical plane.