Output Q
Relay
QY10 16 points, 24 V DC/240 V AC, 2 A/point, 8 A/common, response time: 12 ms, 16 points/common, 18-point terminal block
QY18A 8 points, 24 V DC/240 V AC, 2 A/point, response time: 12 ms, 18-point terminal block, all points independent
Triac
QY22 16 points; 100 to 240 V AC; 0.6 A/point; 4.8 A/common; minimum load voltage/current: 24 V AC/100 mA, 100 to 240 V AC/25 mA; response time: 1 ms + 0.5 cycle, 16 points/common, 18-point terminal block, with surge suppressor
Transistor (Sink)
QY40P 16 points, 12 to 24 V DC, 0.1 A/point, 1.6 A/common, response time: 1 ms, 16 points/common, sink type, 18-point terminal block, with thermal and short-circuit protection and surge suppressor
QY41P (Note 3) 32 points, 12 to 24 V DC, 0.1 A/point, 2 A/common, response time: 1 ms, 32 points/common, sink type, 40-pin connector, with thermal and short-circuit protection and surge suppressor
QY42P (Note 3) 64 points, 12 to 24 V DC, 0.1 A/point, 2 A/common, response time: 1 ms, 32 points/common, sink type, 40-pin connector, with thermal and short-circuit protection and surge suppressor
QY50 16 points, 12 to 24 V DC, 0.5 A/point, 4 A/common, response time: 1 ms, 16 points/common, sink type, 18-point terminal block, with surge suppressor and fuse
Transistor (Independent)
QY68A 8 points, 5 to 24 V DC, 2 A/point, 8 A/module, response time: 10 ms, sink/source type, 18-point terminalblock , with surge suppressor, all points independent
TTL CMOS
QY70 16 points, 5 to 12 V DC, 16 mA/point, 256 mA/common, response time: 0.5 ms, 16 points/common, sink type, 18-point terminal block, with fuse
QY71(Note 3) 32 points, 5 to 12 V DC, 16 mA/point, 512 mA/common, response time: 0.5 ms, 32 points/common, sink type,40-pin connector, with fuse
Transistor (Source)
QY80 16 points, 12 to 24 V DC, 0.5 A/point, 4 A/common, response time: 1 ms, 16 points/common, source type, 18-point terminal block, with surge suppressor and fuse
QY81P(Note 4) 32 points, 12 to 24 V DC, 0.1 A/point, 2 A/common, response time: 1 ms, 32 points/common, source type, 37-pin D-sub connector, with thermal and short-circuit protection and surge suppressor