| Type | G3NA-440B | |
| Operate time | DC input | 1/2 of load power source cycle + 1 ms max. |
| AC input | 1 1/2 of load power source cycle + 1 ms max. | |
| Release time | DC input | 1/2 of load power source cycle + 1 ms max. |
| AC input | 1 1/2 of load power source cycle + 1 ms max. | |
| Output ON voltage drop | 1.8 V (RMS max.) | |
| Leakage current | 10 mA max. at 200 VAC | |
| 20 mA max. at 400 VAC | ||
| Insulation resistance | 100 MΩ min at 500 VDC | |
| Dielectric strength | 2,500 VAC, 50/60 Hz for 1 minute | |
| Vibration | Malfunction | 10 to 55 Hz, 1.5 mm double amplitude |
| Shock | Malfunction | 1,000 m/s2 (approx. 100G) |
| Ambient temperature | Operating | -30° to 80°C (-22° to 176°F) with no icing |
| Storage | -30° to 100°C (-22° to 212°F) with no icing | |
| Humidity | 45% to 85% RH | |
| Weight | Approx. 80 g (2.8 oz.) | |


This website uses cookies (Learn more) and has a privacy policy (Learn more).