Fluke 355 True-rms 2000 A Clamp Meters

฿28650.00
Includes: <br>
Fluke 355 Clamp Meter; <br>
C43 Soft carrying case; <br>
(6) AA batteries; <br>
TL224 1.5 m silicone rubber test leads;
เหลือ 0 ชิ้น
ซื้อเลย
หยิบลงตะกร้า
  • หมวดหมู่ : Clamp Meters
  • รหัสสินค้า : 006680

รายละเอียดสินค้า Fluke 355 True-rms 2000 A Clamp Meters

 

Electrical specifications
Current measurement dc and ac 10 Hz to 100 Hz
Range : 40 A Resolution: 10 mA
Accuracy, A: 1.5 % rdg + 15 digits
Trigger Level for Inrush: 0.50 A
Trigger Level for Hz Filter OFF: 2.50 A
Trigger Level for Hz Filter ON: 0.50 A
Range : 400 A Resolution: 100 mA
Accuracy, A: 1.5 % rdg + 5 digits
Trigger Level for Inrush: 5.0 A
Trigger Level for Hz Filter OFF: 2.5 A
Trigger Level for Hz Filter ON: 2.5 A
Range : 2000 A; 1400 ac rms Resolution: 1 A
Accuracy, A: 1.5 % rdg + 5 digits
Trigger Level for Inrush: 5 A
Trigger Level for Hz Filter OFF: 8 A
Trigger Level for Hz Filter ON: 8 A
Crest Factor (50/60 Hz)
Range : 40 A Crest Factor* : 2 @ 33 A, 2.4 @ 27 A
Range : 400 A Crest Factor* : 2 @ 330 A, 2.4 @ 270 A
Range : 2000 A; 1400 ac rms Crest Factor* : 2 @ 1000 A, 2.4 @ 833 A
Current measurement ac 100.1 Hz to 1 kHz
Range : 40 A Resolution: 10 mA 
Accuracy > 10 A : 3.5 % rdg + 15 digits
Trigger Level for Inrush: 0.50 A
Trigger Level for Hz Filter OFF : 2.50 A
Trigger Level for Hz Filter ON : 0.50 A
Range : 400 A Resolution: 100 mA
Accuracy > 10 A : 3.5 % rdg + 5 digits
Trigger Level for Inrush: 5.0 A
Trigger Level for Hz Filter OFF : 2.5 A
Trigger Level for Hz Filter ON : 2.5 A
Range : 2000 A; 1400 ac rms Resolution: 1 A 
Accuracy > 10 A : 3.5 % rdg + 5 digits
Trigger Level for Inrush: 5 A
Trigger Level for Hz Filter OFF : 8 A
Trigger Level for Hz Filter ON : 8 A
Voltage measurement (355 only) dc and ac 10 Hz to 100 Hz (600 V and 1000 V ranges have 10 % over range to 660 V and 1100 V respectively.)
Range : 4 V Resolution: 1 mV
Accuracy: 1 % rdg + 10 digits
Trigger Level for Hz Filter OFF: 0.050 V
Trigger Level for Hz Filter ON: 0.050 V
Range : 40 V Resolution: 10 mV 
Accuracy: 1 % rdg + 5 digits
Trigger Level for Hz Filter OFF: 0.25 V
Trigger Level for Hz Filter ON: 0.25 V
Range : 400 V Resolution: 100 mV 
Accuracy: 1 % rdg + 5 digits
Trigger Level for Hz Filter OFF: 6 V
Trigger Level for Hz Filter ON: 6 V
Range : 600 V ac rms Resolution: 1 V 
Accuracy: 1 % rdg + 5 digits
Trigger Level for Hz Filter OFF: 6 V
Trigger Level for Hz Filter ON: 6 V
Range : 1000 V dc Resolution: 1 V 
Accuracy: 1 % rdg + 5 digits
Voltage measurement (355 only) ac 100.1 Hz to 1 kHz (600 V and 1000 V ranges have 10 % over range to 660 V and 1100 V respectively.)
Range: 4 V Resolution: 1 mV
Accuracy: 3 % rdg + 10 digits
Trigger Level for Hz Filter OFF: 0.050 V
Trigger Level for Hz Filter ON: 0.050 V
Range: 40 V Resolution: 10 mV
Accuracy: 3 % rdg + 5 digits
Trigger Level for Hz Filter OFF: 0.25 V
Trigger Level for Hz Filter ON: 0.25 V
Range: 400 V Resolution: 100 mV
Accuracy: 3 % rdg + 5 digits
Trigger Level for Hz Filter OFF: 6 V
Trigger Level for Hz Filter ON: 6 V
Range: 600 V ac rms Resolution: 1 V
Accuracy: 3 % rdg + 5 digits
Trigger Level for Hz Filter OFF: 6 V
Trigger Level for Hz Filter ON: 6 V
Ohms measurement (355 only)
Range: 400 Ω Resolution: 0.1 Ω
Accuracy: 1.5 % + 5 digits
Range: 4 kΩ Resolution: 1 Ω
Accuracy: 1.5 % + 5 digits
Range: 40 kΩ Resolution: 10 Ω
Accuracy: 1.5 % + 5 digits
Range: 400 kΩ Resolution: 100 Ω
Accuracy: 1.5 % + 5 digits
Continuity beeper (355 only) On at ≤ 30 Ω
Off at ≥ 100 Ω
Frequency measurement
Measurement range 5.0 Hz to 1 kHz
Resolution 0.1 Hz (15 Hz to 399.9 Hz); 1 Hz (400 Hz to 1 kHz)
Accuracy – 5.0 Hz to 100 Hz 0.2 % + 2 counts
Accuracy – 100.1 Hz to 1 kHz 0.5 % + 5 counts
Trigger level Refer to current and voltage tables
*Add 2 % to error spec for CF > 2
General specifications
Batteries
Six 1.5 V AA NEDA 15 A or IEC LR6
Battery life (with typical usage, backlight off) 100 hours
Test leads Rated to 1000 V
Weight .814 kg (1.8 lb)
Jaw size 58 mm (2.28 in)
Dimensions (LxWxD) 300 mm x 98 mm x 52 mm (12 in x 3.75 in x 2 in)
Safety rating IEC 61010-2-032, 600 V CAT IV, 1000 V CAT III
Environmental specifications
Operating temperature 32 °F to + 122 °F (0 °C to +50 °C)
Storage temperature -4 °F to 140 °F (-20 °C to +60 °C)
Operating humidity 0 to 95 % (non-condensing)
Operating altitude 2000 m
Storage altitude 10,000 m
IP rating 42 (indoor use only)
Drop test requirements 1 m
EMI, RFI, EMC FCC part 15, IEC/EN 61326-1:1997 class B, IEC/EN 61326:1997 3V/m, performance criteria B, EN61325
Temperature coefficients
Current: 0.1 % of reading per °C outside 22 °C to 24 °C
Voltage 0.1 % of reading per °C outside 22 °C to 24 °C