Item Contact output Solid-state output
Rated supply voltage 100 to 240 VAC (50/60 Hz), 12 to 48 VDC
(permissible ripple: 20% max.) 
(See note 1.)
12 to 48 VDC (permissible ripple: 20% max.)
Operating voltage range 85% to 110% of rated supply voltage
Power consumption Approx. 12 VA at 240 VAC, 50 Hz
Approx. 2.5 W at 48 VDC
Approx. 2.5 W at 48 VDC
Mounting method Surface mounting or flush mounting
Display 7-segment LEDs (8-mm-high characters), UP indicator
Input method Contact open and short-circuit input Open-collector transistor ON/OFF input
Resetting system and gate input Reset by power-OFF (See note 2.): 
min. power OFF time: 0.5 s 
External reset or gate (common to contact and solid-state inputs): min. reset input signal width: 0.02 s; 
residual voltage: 2 V max.
Output mode N mode (Power ON-delay)
Control outputs SPDT: 3 A at 250 VAC, resistive load (cosΦ = 1) Open collector: 100 mA max. at 30 VDC max.
Ambient temperature Operating:-10°C to 55°C (with no icing or condensation) 
Storage:-25°C to 65°C (with no icing or condensation)
Ambient humidity Operating: 35% to 85%
Case color Light gray (Munsell 5Y7/1)

 

Note:Note:

Note:Models with memory backup function are available only for AC power.

Note:The H5CN-X[]NM cannot be reset by turning OFF the power.

Characteristics

 

Accuracy of operating time ±0.01% ±0.05 s max. (see note 1), ±0.005% ±0.03 s max. (see note 2) (see note 3)
Setting error
Influence of voltage
Influence of temperature
Insulation resistance 100 MΩ min. (at 500 VDC) (between current-carrying terminal and exposed non-current carrying metal parts, between power supply circuit and control output circuit)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminal and exposed non-current-carrying metal parts, between power supply circuit and control output circuit)
Impulse withstand voltage 6 kV (between power supply terminal)
6 kV (between current-carrying terminal and exposed non-current carrying metal parts)
Noise immunity Square-wave noise by noise simulator
AC: ±2 kV (between power supply terminals)
DC: ±480 V (between power supply terminals), ±500 V (between input terminals)
Static immunity Malfunction: 8 kV
Vibration resistance Destruction:10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each
Malfunction:10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each
Shock resistance Destruction:300 m/s2 3 times each in 6 directions
Malfunction:100 m/s2 3 times each in 6 directions
Life expectancy Mechanical:10,000,000 operations min.
Electrical:100,000 operations min. (3 A at 250 VAC, resistive load)
Approved standards UL508, CSA C22.2 No. 14